Panel mounting – Rockwell Automation 1762-OW8 MICROLOGIX RELAY OUTPUT MODULE User Manual

Page 6

Advertising
background image

6

MicroLogix 1762-OW8 Relay Output Module

Publication 1762-IN003B-EN-P - June 2013

Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35) for
vibration or shock environments.

Panel Mounting

Use the dimensional template shown below to mount the module. The preferred mounting
method is to use two M4 or #8 panhead screws per module. M3.5 or #6 panhead screws may also
be used, but a washer may be needed to ensure a good ground contact. Mounting screws are
required on every module.

TIP

For environments with greater vibration and shock concerns, use the panel
mounting method described below, instead of DIN rail mounting.

End Anchor

End Anchor

MicroLogix 1200

Controller

MicroLogix 1200

Expansion I/O

MicroLogix 1200

Expansion I/O

MicroLogix 1200

Expansion I/O

90
(3.54)

100
(3.94)

40.4
(1.59)

40.4
(1.59)

14.5
(0.57)

For more than 2 modules: (number of modules - 1) x 40 mm (1.58 in.)

NOTE: All dimensions are in mm (inches). Hole spacing
tolerance: ±0.4 mm (0.016 in.).

Advertising