Field Wiring Connections

Grounding the Module

This product is intended to be mounted to a well-grounded mounting surface such as a metal
panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used)
are not required unless the mounting surface cannot be grounded. Refer to Industrial
Automation Wiring and Grounding Guidelines, Allen-Bradley publication

1770-4.1

, for

additional information.

Output Wiring

Basic wiring

(1)

of the 1762-OW8 is shown below.

A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.

(1)

Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication

1770-4.1

.

ATTENTION

!

Be careful when stripping wires. Wire fragments that fall into a module could
cause damage when power is applied. Once wiring is complete, ensure the
module is free of all metal fragments.

OUT 5

VAC-VDC

1

OUT 2

OUT 0

OUT 7

OUT 4

OUT 3

OUT 1

VAC-VDC

0

OUT 6

CR

CR

CR

CR

CR

CR

L1 or +DC

L2 or -DC

L1 or +DC

L2 or -DC