MicroLogix 1762-OW8 Relay Output Module

13

Publication 1762-IN003B-EN-P - June 2013

Power supply distance rating

6

Isolated groups

Group 1: Outputs 0…3
Group 2: Outputs 4…7

Output group to backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 sec. or
2596V DC for 1 sec.
265V AC working voltage (IEC Class 2 reinforced insulation)

Output group to output group isolation Verified by one of the following dielectric tests: 1836V AC for 1 sec. or

2596V DC for 1 sec.
265V AC working voltage (basic insulation)

150V AC working voltage (IEC Class 2 reinforced insulation)

Vendor ID code

1

Product type code

7

Product code

120

Relay Contact Ratings

Volts (max.)

Continuous
Amps per Point
(max.)

Amperes

(1)

(1)

Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication

1770-4.1

.

Voltamperes

Make

Break

Make

Break

240V AC

2.5 A

7.5 A

0.75 A

1800 VA

180 VA

120V AC

15 A

1.5 A

125V DC

1.0 A

0.22 A

(2)

(2)

For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58 A. For DC voltage applications less than 48V, the make/break rating
for relay contacts cannot exceed 2A.

28 VA

24V DC

2.0 A

1.2 A

28 VA

Output Specifications

Specification

Value