Advanced setup parameters – Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 42

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

32 Configure Your Module

Advanced Setup Parameters

Advanced parameters you can set for the RTD module consist of:

• Notch filter – Select the Notch Filter for the analog to digital converter.

At higher frequencies, faster sample rates are possible

50 Hz
60 Hz (default)
100 Hz
120 Hz
200 Hz
240 Hz
300 Hz
400 Hz
480 Hz

If the filter value is changed, the module may require calibration to meet
specifications.

• Digital filter – A digital filter is available on this module. You set a time

constant that is used in the equation:

Yn = Yn-1 + (dt / (dt + T

A

) * (Xn-Yn-1)

Where: Yn = new data
Yn-1 = old data
dt = Channel Update Rate in milliseconds

T

A

= digital filter time constant

Xn = present unfiltered data

T

A

can be an integer from 0 to 10,000 ms. If set to 0, the filter is

disabled.

• Enable alarms latch – If enabled, alarms for this channel latch

FAULTED until a Latch Reset command is received.
The alarms effected are:

Input Status
Low and High level
Range

• Disable alarms – If Alarms are Disabled, all alarms for this channel

show No FAULT. This is useful for unused channels.

• Level alarms – low-low, low, high, and high-high.