Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 43

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

Configure Your Module 33

• Scaling – Values returned when input is at low scale value or high scale

value. The low and high scale points are different for each sensor input:

To configure your RTD module, select Configuration as shown in the figure.

Use the procedures in the figures that show basic setup and advanced setup,
noting that you complete steps 1 and 2 during basic setup, then continue with
steps 3…13 during advanced setup.

RTD Module Scaling Limits

RTD Type

Low Scaling
Endpoint

High Scaling
Endpoint

O hms

100

Ω

500

Ω

100

Ω

Pt

α =

0.00385 Euro

32 °F (0 °C)

932 °F (500 °C)

200

Ω

Pt

α =

0.00385 Euro

32 °F (0 °C)

932 °F (500 °C)

100

Ω

Pt

α =

0.003916 U.S.

32 °F (0 °C)

932 °F (500 °C)

200

Ω

Pt

α =

0.003916 U.S.

32 °F (0 °C)

932 °F (500 °C)

10

Ω

Cu

α =

0.00427

32 °F (0 °C)

482 °F (250 °C)

100

Ω

Ni

α =

0.00618

32 °F (0 °C)

482 °F (250 °C)

120

Ω

Ni

α =

0.00672

32 °F (0 °C)

482 °F (250 °C)

120

Ω

Ni

α =

0.00618

32 °F (0 °C)

482 °F (250 °C)

RTD Type (1734-IR2E)

Low Scaling
Endpoint

High Scaling
Endpoint

O hms

100

Ω

200

Ω

100

Ω

Pt

α =

0.00385 Euro

32 °F (0 °C)

572 °F (300 °C)

1. To configure your RTD module,

select Configuration and
modify the parameters as
desired for your application.

2. When complete, download to

your module by clicking the
Download to Device button.
You can download each
change as you make it using
Single, or download all your
changes using All. If you press
the Apply button, only the
selected parameter
downloads to the module.

3. Click here when finished.