50 Calibrate Your Module
5. From the Device Parameters dialog, select Calibration at the Groups
pull-down.
6. Click Calibration Command and select Begin Calibration.
7. Click the Download to Device button.
Both channel status indicators turn off.
8. From the General Parameters dialog, click the Download to Device
button.
9. Using a 0.05 % accurate resistance box, apply 100.00
Ω
to the input,
assuming that you have selected Ohms as the RTD type for the channel
being calibrated.
This is the Groups pull-down menu.
Select Begin Calibration on the
calibration command pull-down
menu.