Publication 1734-UM004F-EN-E - December 2012

50 Calibrate Your Module

5. From the Device Parameters dialog, select Calibration at the Groups

pull-down.

6. Click Calibration Command and select Begin Calibration.

7. Click the Download to Device button.

Both channel status indicators turn off.

8. From the General Parameters dialog, click the Download to Device

button.

9. Using a 0.05 % accurate resistance box, apply 100.00

Ω

to the input,

assuming that you have selected Ohms as the RTD type for the channel
being calibrated.