Simultaneous mode (two channels) input file – Rockwell Automation 1769-ASCII Compact Module User Manual

Page 19

Advertising
background image

Compact 1769-ASCII Module 19

Publication

1769-IN068B-EN-P - May 2005

Simultaneous Mode (Two Channels) Input File

Maximum size is shown below. Refer to the Compact I/O 1769-ASCII
Module User Manual, publication 1769-UM012, to use smaller output files.

• Tx = Transmit
• Rx = Receive
• TG = Transmit greater than Max Error. Transmit length in the output

file is greater than the maximum transmit character length in the
configuration file.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Channel 0 Data

0

Tx ID Acknowledged

Rx Transaction ID

1

Reserved

TG

TS ND HE NR

RF

TF

PA RO TO

2

Firmware Revision, Major

Firmware Revision, Minor

3

Length (Number of Bytes)

4

Character 1

Character 0

5

Character 3

Character 2

Character …

Character …

x

(1)

(1)

X is calculated based on the size of Channel 0 data as specified in the input file. Both channels
cannot contain 200 characters as the total configuration file size can be only 108 words.

Last Character

Character …

Channel 1 Data

x+1

Tx ID Acknowledged

Rx Transaction ID

x+2

Reserved

TG

TS ND HE NR

RF

TF

PA RO TO

x+3

Firmware Revision, Major

Firmware Revision, Minor

x+4

Length (Number of Bytes)

x+5

Character 1

Character 0

x+6

Character 3

Character 2

Character …

Character …

y

(2)

(2)

Y is equal to the connection size minus 1, with a maximum value of 107 for a buffer size of 108.

Last Character

Character …

Advertising