Troubleshoot with error codes, Configuration error codes – Rockwell Automation 1769-ASCII Compact Module User Manual

Page 33

Advertising
background image

Compact 1769-ASCII Module 33

Publication

1769-IN068B-EN-P - May 2005

Troubleshoot with Error Codes

Configuration Error Codes

Value (Hex)

Meaning

0

No error

200…3FF

Hardware error

400…5FF

Configuration error

800…DFF

Reserved for future use

E00…FFF

Bus master detected error

Value
(Hex)

Meaning

Description

Global Module Errors

0

No error

The 1769-ASCII module adds no
module-specific errors.

401

Max output array size exceeded

The maximum output array size is too
large.

In alternating mode, channel 0 and
channel 1 must have less than 496
transmit characters.

In simultaneous mode, channel 0 and
channel 1 must have less than 496
transmit characters collectively.

402

Max input array size exceeded

The maximum input array size is too
large.

In alternating mode, channel 0 and
channel 1 must have less than 496
receive characters.

In simultaneous mode, channel 0 and
channel 1 must have less than 496
receive characters collectively.

Advertising