Simultaneous Mode (Two Channels) Output File

Maximum size is shown below. Refer to the Compact I/O 1769-ASCII
Module User Manual, publication 1769-UM012, to use smaller output files.

• Tx = Transmit
• Rx = Receive

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Channel 0 Data

0

Reserved

Tx Transaction ID

1

Reserved

Rx Transaction ID Request

2

Reserved

3

Length (Number of Bytes)

4

Character 1

Character 0

5

Character 3

Character 2

Character …

Character …

x

(1)

(1)

X is calculated based on the size of Channel 0 data as specified in the configuration file. Both
channels cannot contain 200 characters as the total configuration file size can be only 108 words.

Last Character

Character …

Channel 1 Data

x+1

Reserved

Tx Transaction ID

x+2

Reserved

Rx Transaction ID Request

x+3

Reserved

x+4

Length (Number of Bytes)

x+5

Character 1

Character 0

x+6

Character 3

Character 2

Character …

Character …

y

(2)

(2)

Y is equal to the connection size minus 1, with a maximum value of 107 for a buffer size of 108.