Configuration file – Rockwell Automation 1769-ASCII Compact Module User Manual

Page 22

Advertising
background image

22 Compact 1769-ASCII Module

Publication

1769-IN068B-EN-P - May 2005

Configuration File

The 1769-ASCII module supports a configuration assembly that is accessible
through the Assembly Object (Class 4), Instance 102. The configuration
assembly is 31 words. The addresses assume a 16-bit data structure where all
16-bit values are INT

(1)

. The least significant word occupies the smaller byte

addresses.

(1)

INT = Integer range of -32768 to +32767 decimal, 0000 to FFFF hexadecimal.

Wo

rd

Description

Values

Valid Data Values

0

Data Buffer Mode

0…1

0 = alternate mode

1 = simultaneous mode

Channel 0

1

Serial Character Framing

0…8

0 = 7N2, 1 = 7E1, 2 = 7O1, 3 = 8N1, 4 =
8N2, 5 = 8E1, 6 = 8O1, 7 = 7E2, 8 = 7O2

2

Serial Port Speed

0…7

0 = 9600, 1 = 1200, 2 = 2400, 3 = 4800, 4
= 19200, 5 = 38400, 6 = 57.6k, 7 = 115.2k
(half-duplex only)

Serial Port Receive Data

3

Max Number of Receive
Characters

0…200

In Simultaneous mode, the total number
of channel 0 characters plus channel 1
characters cannot exceed 200.

4

Receive Record Start Mode

0…2

0 = ignore, 1 = exclude, 2 = include start
delimiter

5

Receive Start Delimiter

(1)

0…127/255

0…0x7f (0…127) for 7-bit data

0…0xff (0…255) for 8-bit data

6

Receive Record End Mode

0…2

0 = ignore, 1 = exclude, 2 = include end
delimiter

7

Receive End Delimiter

(1)

0…127/255

0…0x7f (0…127) for 7-bit data

0…0xff (0…255) for 8-bit data

Advertising