Rockwell Automation 1769-ASCII Compact Module User Manual

Page 31

Advertising
background image

Compact 1769-ASCII Module 31

Publication

1769-IN068B-EN-P - May 2005

Conducted RF Immunity

IEC 61000-4-6:

10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80
MHz

Enclosure Type Rating

None (open-style)

Dimensions (HxWxL),
Imperial

3.39 x 1.33 x 4.60 in

Dimensions (HxWxL), Metric

87 x 34 x 118 mm

Serial Port Connectors

Two DB-9 male (with pins)

Conductors Category

2

1

Weight, Imperial

0.4 lb

Weight, Metric

0.18 kg

Certifications (when product
is marked)

c-UL-us

2

- UL Listed for Class I, Division 2 Group A, B, C, D

Hazardous Locations, certified for U.S. and Canada

CE

2

- European Union 89/335/EEC EMC Directive,

compliant with:

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

C-Tick

2

- Australian Radiocommunications Act, compliant

with: AS/NZS CISPR 11; Industrial Emissions

1

Use this conductor category information for planning conductor routing as described in publication
1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.”

2

See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and
other certification details.