Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual
Page 17

Publication 1746-UM001A-US-P
Quick Start for Experienced Users 2-3
3.
Insert the 1746-NI16 module into the chassis.
Reference
ATTENTION
!
Never install, remove, or wire modules with power applied to the chassis or devices
wired to the module.
Make sure system power is off; then insert the module into your 1746 chassis.
In this example procedure, local slot 1 is selected. Any slot may be used except 0.
Chapter 3
(Installation and
Wiring)
Top and Bottom
Module Releases
Card
Guide
4.
Connect sensor cable.
Reference
Connect sensor cable to the module’s terminal block.
Important: Follow these guidelines when wiring the module:
•
Use shielded communication cable (Belden™ 8761) and keep length as short as possible.
•
Connect only one end of the cable shield to earth ground.
•
Connect all the shields to the earth ground at the SLC 500™ chassis mounting tab.
•
Single-ended source commons may be jumpered together at the terminal block.
•
Channels are not isolated from each other. All analog commons are connected together internally.
•
Common mode voltage range is ±10.25 volts. The voltage between any two terminals must be less than
20.5 volts.
•
The module does not provide power for the analog input transmitters or sensors.
•
Use a power supply that matches the transmitter (sensor) specifications.
Chapter 3
(Installation and
Wiring)
Sensor Cable
Terminal Block
IN 0
IN 2
IN 4
IN 6
IN 1
IN 3
IN 5
IN 7
Analog Com
Analog Com