Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual

Page 57

Advertising
background image

Publication 1746-UM001A-US-P

Channel Configuration, Data, and Status 5-9

The channel data word contains a 16-bit integer that represents the
value of the analog input channel. The tables below show the channel
data word values for various input types and data formats. The second
table shows the default full-scale values for the proportional counts
data format. The table does not imply the entire data value range is
usable resolution.

Class 3 Data Word

I:e.0

channel 0 data word

16-bit integer

I:e.1

channel 1 data word

16-bit integer

I:e.2

channel 2 data word

16-bit integer

I:e.3

channel 3 data word

16-bit integer

I:e.4

channel 4 data word

16-bit integer

I:e.5

channel 5 data word

16-bit integer

I:e.6

channel 6 data word

16-bit integer

I:e.7

channel 7 data word

16-bit integer

I:e.8

channel 8 data word

16-bit integer

I:e.9

channel 9 data word

16-bit integer

I:e.10

channel 10 data word

16-bit integer

I:e.11

channel 11 data word

16-bit integer

I:e.12

channel 12 data word

16-bit integer

I:e.13

channel 13 data word

16-bit integer

I:e.14

channel 14 data word

16-bit integer

I:e.15

channel 15 data word

16-bit integer

Channel Data Word Values for Engineering Units

Input Type

Signal Range

Engineering Units

Engineering Units
Scale

±10V dc

-10.25V to +10.25V

-10250 to +10250

1 mV/step

0 to 5V dc

-0.25V to +5.25V

-250 to +5250

1 mV/step

1 to 5V dc

+0.75V to +5.25V

+750 to +5250

1 mV/step

0 to 10V dc

-0.5V to +10.25V

-500 to +10250

1 mV/step

0 to 20 mA

-1.0 mA to 21 mA

-1000 to +21000

1.0 µA/step

4 to 20 mA

3.0 mA to 21mA

3000 to 21000

1.0 µA/step

±20 mA

-21 mA to 21 mA

-21000 to +21000

1.0 µA/step

0 to 1 mA

-0.05 mA to 1.05 mA

-50 to +1050

1.0 µA/step