Channel configuration word -3, Channel configuration word – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual
Page 51

Publication 1746-UM001A-US-P
Channel Configuration, Data, and Status 5-3
Channel Configuration Word
Define
To Select
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Class 1
Data or Status
Configuration
Read Data for Channel 0 to 7
0
0
Read Data for Channel 8 to 15
0
1
Read Status for Channel 0 to 7
1
0
Read Status for Channel 8 to 15
1
1
Class 1 Handshaking
To Reset Status Bit 6
0
Transmit Channel Configuration
1
Reserved
Not Used
X
Input Type
+/- 10 Vdc or +/- 20 ma
0
0
1 to 5 Vdc or 4 to 20 ma
0
1
0 to 5 Vdc or 0 to 1 ma
1
0
0 to 10 Vdc or 0 to 20 ma
1
1
Data Format
Engineering Units
0
0
0
Scaled-for-PID
0
0
1
Proportional Counts
0
1
0
1746-NI4 Data Format
0
1
1
User Limit Range 0 (Class 3 Only)
1
0
0
User Limit Range 1 (Class 3 Only)
1
0
1
User Limit Range 2 (Class 3 Only)
1
1
0
User Limit Range 3 (Class 3 Only)
1
1
1
Calibration
Channel needs to be
disabled to perform
calibration
Normal RUN Mode (Exit Calibration
Mode)
0
0
0
Enter Calibration Mode
0
0
1
Perform Zero Calibration
0
1
1
Perform Full Scale Calibration
1
0
1
Filter Frequency
Filter frequencies are set
in ch 0, 4, 8 and 12 for that
channel and the following
3 channels in that group.
Filter groupings are:
(0 to 3) (4 to 7) (8 to 11)
and (12 to 15)
6 Hz
0
0
0
10 Hz
0
0
1
20 Hz
0
1
0
40 Hz
0
1
1
60 Hz
1
0
0
80 Hz
1
0
1
100 Hz
1
1
0
250 Hz
1
1
1
Channel Enable
Channel Disabled
0
Channel Enabled
1