Channel configuration word -3, Channel configuration word – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual

Page 51

Advertising
background image

Publication 1746-UM001A-US-P

Channel Configuration, Data, and Status 5-3

Channel Configuration Word

Define

To Select

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Class 1
Data or Status
Configuration

Read Data for Channel 0 to 7

0

0

Read Data for Channel 8 to 15

0

1

Read Status for Channel 0 to 7

1

0

Read Status for Channel 8 to 15

1

1

Class 1 Handshaking

To Reset Status Bit 6

0

Transmit Channel Configuration

1

Reserved

Not Used

X

Input Type

+/- 10 Vdc or +/- 20 ma

0

0

1 to 5 Vdc or 4 to 20 ma

0

1

0 to 5 Vdc or 0 to 1 ma

1

0

0 to 10 Vdc or 0 to 20 ma

1

1

Data Format

Engineering Units

0

0

0

Scaled-for-PID

0

0

1

Proportional Counts

0

1

0

1746-NI4 Data Format

0

1

1

User Limit Range 0 (Class 3 Only)

1

0

0

User Limit Range 1 (Class 3 Only)

1

0

1

User Limit Range 2 (Class 3 Only)

1

1

0

User Limit Range 3 (Class 3 Only)

1

1

1

Calibration
Channel needs to be
disabled to perform
calibration

Normal RUN Mode (Exit Calibration
Mode)

0

0

0

Enter Calibration Mode

0

0

1

Perform Zero Calibration

0

1

1

Perform Full Scale Calibration

1

0

1

Filter Frequency
Filter frequencies are set
in ch 0, 4, 8 and 12 for that
channel and the following
3 channels in that group.
Filter groupings are:
(0 to 3) (4 to 7) (8 to 11)
and (12 to 15)

6 Hz

0

0

0

10 Hz

0

0

1

20 Hz

0

1

0

40 Hz

0

1

1

60 Hz

1

0

0

80 Hz

1

0

1

100 Hz

1

1

0

250 Hz

1

1

1

Channel Enable

Channel Disabled

0

Channel Enabled

1