Scaled-for-pid to real units, Proportional counts to real units – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual
Page 62

Publication 1746-UM001A-US-P
5-14 Channel Configuration, Data, and Status
Scaled-for-PID to Real Units
Example: #3 A transducer is being used to measure temperature.
The 4 to 20 mA signal range is proportional to 100 to 500°C (212 to 932°F)
The input data is scaled for PID, i.e. input range of 0 to 16383
Input value to convert = 5500
The scaled range is 212 to 932°F
The Input range is 0 to 16383
Find: Input value in °F
Per the equation above:
Proportional Counts to Real Units
Example: #4 A transducer is being used to measure pressure.
The -10V dc to +10V dc signal range is proportional to 0 to 200 psi
The input data is in “Proportional Counts” data format, i.e. -32768 to 32767
Input value to convert = 21567
The Scaled range is 0 to 200 psi
The Input range is -32768 to 32767
Find: Input value in psi
Per the equation above:
Slope
932
212
–
(
)
16383
0
–
(
)
--------------------------------
0.044
=
=
Offset
212
0
0.044
×
(
)
212
=
–
=
Scaled Value
5500
0.044
×
(
)
212
454
°
F
=
+
=
Slope
200
0
–
(
)
32767
32768
–
(
)
–
[
]
------------------------------------------------------
0.003
=
=
Offset
0
32768 0.003
(
)
–
(
)
98.3
=
–
=
Scaled Value
21567
003
×
(
)
98.3
163 psi
=
+
=