5 - channel configuration, data, and status, Channel configuration, Chapter 5 – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual
Page 49: Channel configuration, data, and status, Channel configuration -1, Chapter

1
Publication 1746-UM001A-US-P
Chapter
5
Channel Configuration, Data, and Status
This chapter examines the channel configuration word and the
channel status word bit by bit and explains how the module uses
configuration data and generates status during operation. It gives you
information about how to:
•
configure a channel
•
scale the channel data
•
check a channel’s status
Channel Configuration
The channel configuration word is a part of the 1746-NI16 module’s
output image as shown below. The module output image uses 8
words when the module is in Class 1 mode and 32 words when the
module is in Class 3 mode. A description of the output image is
shown below.
1746-NI16 Module Output Image - Channel Configuration
Class 1
Class 3
O:e.0
channel 0 configuration word
bit-mapped field
•
•
O:e.1
channel 1 configuration word
bit-mapped field
•
•
O:e.2
channel 2 configuration word
bit-mapped field
•
•
O:e.3
channel 3 configuration word
bit-mapped field
•
•
O:e.4
channel 4 configuration word
bit-mapped field
•
•
O:e.5
channel 5 configuration word
bit-mapped field
•
•
O:e.6
channel 6 configuration word
bit-mapped field
•
•
O:e.7
channel 7 configuration word
bit-mapped field
•
•
O:e.8
channel 8 configuration word
bit-mapped field
•
O:e.9
channel 9 configuration word
bit-mapped field
•
O:e.10
channel 10 configuration word
bit-mapped field
•
O:e.11
channel 11 configuration word
bit-mapped field
•
O:e.12
channel 12 configuration word
bit-mapped field
•
O:e.13
channel 13 configuration word
bit-mapped field
•
O:e.14
channel 14 configuration word
bit-mapped field
•
O:e.15
channel 15 configuration word
bit-mapped field
•
O:e.16
lower limit range 0
16-bit integer
•
O:e.17
upper limit range 0
16-bit integer
•
O:e.18
lower limit range 1
16-bit integer
•
O:e.19
upper limit range 1
16-bit integer
•
O:e.20
lower limit range 2
16-bit integer
•
O:e.21
upper limit range 2
16-bit integer
•
O:e.22
lower limit range 3
16-bit integer
•
O:e.23
upper limit range 3
16-bit integer
•