Chapter 1 Major faults
4. In the Controller Organizer, right-click the program you created in step 2
and choose Add>New Routine.
5. On the New Routine dialog box, in the Name field, enter a name for the
routine.
6. In the Assignment field, use the default setting, Main.
Tip:
Even though you can choose Fault in the Assignment field, assigning the routine as a fault routine
within the Controller Fault Handler is not necessary.
7. Click OK.
The fault routine is created in the Controller Fault Handler program. If you
want to edit the fault routine, double-click it to open it.