Programmatically clear a major fault, Create a data type to store fault information – Rockwell Automation Logix5000 Controllers Major, Minor, and I/O Faults Programming Manual User Manual

Page 21

Advertising
background image

Major faults Chapter 1

7. Click OK. The fault routine is added to the Power-Up Handler. If you

want to edit the new routine, double-click it to open it.

To clear a major fault that occurs during the execution of your project, see the

following sections and complete the actions in the appropriate routine.

Create a Data Type to store fault information on page 21

.

Get the fault type and code on page 25

.

Check for a specific fault on page 26

.

Clear the fault on page 26

.

Important: Do not use fault routines to continually clear all faults on the controller. Program the fault routine to be

selective in the types and number of faults cleared.

Important: When an instruction generates an error due to a fault (for example, a COP with an indirect addressing

programming error), the instruction is skipped and does not run. This occurs with all instructions.

Create a Data Type to store fault information

Logix5000 controllers store system information in objects. Unlike PLC-5 or SLC

500 controllers, there is no status file.

To access system information, use a Get System Value (GSV) or Set System

Value (SSV) instruction.

For status information about a program, access the PROGRAM object.

For fault information, access the attribute of the PROGRAM object.

Attribute

Data Type

Instruction

Description

MajorFaultRecord

DINT[11]

GSV
SSV

Records major faults for this program.
Specifies the program name to determine which
PROGRAM object you want, or specifies THIS to access
the PROGRAM object for the program that contains the
GSV or SSV instruction.

Programmatically clear a
major fault

Rockwell Automation Publication 1756-PM014G-EN-P – October 2014

21