Rockwell Automation Logix5000 Controllers Major, Minor, and I/O Faults Programming Manual User Manual

Page 38

Advertising
background image

Chapter 2 Minor faults

Type

Code

Cause

Recovery Method

6

4

Virtual adapter task overlap. (CompactLogix 1769-L2x and 1769-L3x
controllers only)
Virtual adapter has not completed running at the rate specified by the
Requested Packet Interval (RPI) when it executed again.

Increase the RPI for the CompactBus.

7

49

Project loaded from nonvolatile memory.

9

0

Unknown error while servicing the serial port.

Contact Rockwell Automation Technical Support.

9

1

The CTS line is not correct for the current configuration.

Disconnect and reconnect the serial port cable to the controller.
Make sure the cable is wired correctly.

9

2

Poll list error.
A fault was detected with the DF1 master’s poll list, such as specifying

more stations than the size of the file, specifying more than 255 stations,
trying to index past the end of the list, or polling the broadcast address
(STN #255).

Check for the following errors in the poll list.

Total number of stations is greater than the space in the poll list tag.

Total number of stations is greater than 255.

Current station pointer is greater than the end of the poll list tag.

A station number greater than 254 was encountered.

9

3

The RS232 DFI Master Active Station tag is unspecified.

Specify a tag to be used for the Active Station Tag in the System Protocol
tab of the Controller Properties.

9

5

DF1 slave poll timeout.
The poll watchdog has timed out for slave. The master has not polled this
controller in the specified amount of time.

Determine and correct delay for polling.

9

9

Modem contact was lost.
DCD or DSR control lines are not being received in proper sequence or
state.

Correct modem connection to the controller.

9

10

Data has been dropped or lost from the serial port.

Slow down the rate at which the initiator is sending data.

10

10

Battery not detected or needs to be replaced.

Install a new battery.

10

11

Safety partner battery not detected or needs to be replaced.

Install a new battery.

10

12

The ESM of a 1756-L7x controller is not installed.
If the controller is powered-down, the WallClockTime attribute and
program are not maintained.

Install an ESM in the controller.

10

13

The ESM installed on the 1756-L7x controller is not compatible with the

controller.

Replace the installed ESM with one that is compatible with the controller.

10

14

The ESM needs to be replaced due to a hardware fault.
It is not capable of maintaining the WallClockTime attribute or controller
program at powerdown.

Replace the ESM.

10

15

The ESM cannot store enough energy to maintain the WallClockTime
attribute or the controller program at power-down.

Replace the ESM.

17

1…n

An internal controller diagnostic has failed.

Contact Rockwell Automation Technical Support with the fault type and
fault code logged.

38

Rockwell Automation Publication 1756-PM014G-EN-P – October 2014