Rockwell Automation 1792D-2BVA2D ArmorBlock MaXum 2 Input with Alarm/2 Output Module Series B User Manual

Page 11

Advertising
background image

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 11

Publication 1792D-IN015B-EN-P - September 2000

The following table describes logic status indicators.

The following table describes auxiliary power indicators.

The following table describes I/O status indicators.

For more information on indications, see the Technical Data,
publication 1792-TD001B-EN-P.

Logic Status Indicators

State

Status

Off

Logic is disabled

Solid Green

Logic is enabled

Flashing Green

Local forces are applied and local logic is enabled

Auxiliary Power

Indication

Status

None

No Auxiliary Power

Solid Green

Auxiliary Power Present

I/O Status Indicators

Function

Module Status Indicator

Point Indicator Condition

Outputs

Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red

None
Yellow
Orange
Red
Orange
Red

Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
Output no load-auto restart
Output no load-latching

Inputs

Green
Green
Module Status blink red

Module Status blink red

None
Yellow
Red

Blink red

No valid input
Valid input
Connector A or Connector B
short circuited
Connector A or Connector B
off-wire

Advertising