12 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B

Publication 1792D-IN015B-EN-P - September 2000

Specifications

2 Input with Alarm / 2 Output Module - Cat. No. 1792D-2BVA2D

Input Specification

Max.

Min.

Inputs per block

2 - 3 wire or dry contact PNP or NPN devices or 2 - 4
wire PNP or NPN devices

Sensor Source Current (per input)

100mA

-

Off-Wire Sense Current

0.5mA

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

Output Specification

Max.

Min.

Outputs per block

2 sourcing outputs labeled 00 and 01

Output Auxiliary Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

1A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

2A

-

Surge Current - for 10ms,
repeatable every 2s

2.4A

-

No Load Sense Current (On-state)

0.18A

-

General Specifications

Indicators

Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red

Communication Rate

•125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters
•250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
•500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters

DeviceNet Power Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.

25V dc max
150mA max (no sensors)

11V dc min up to .8A
(2 sensors @100mA
per sensor)

Auxiliary Power

Voltage
Current

30V dc max
2A max

10V dc min
2A max