6 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B

Publication 1792D-IN015B-EN-P - September 2000

Connect the Cord Sets to the MaXum Module

This module uses 5 pin micro (12mm) style PCB mounted connectors.

Four micro caps cover the connectors on your module. Remove the
caps and connect your cord sets to the appropriate ports.

Use the micro caps to cover and seal unused ports. A pinout diagram
for the connectors is shown next.

Please refer to publication 889-5.0 for Rockwell Automation cables

and cord sets offerings.

IMPORTANT

If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.

Input Micro-Connector

(View into Socket)

Pin 1 Sensor Source Voltage
Pin 2 Alarm

Pin 3 Return Logic Ground

1

Pin 4 Input
Pin 5 Not Used

1

5

3

4

2

41452

Output Micro-Connector

(View into Socket)

Pin 1 Not used
Pin 2 Not used
Pin 3 Auxiliary Power Ground
Pin 4 Output
Pin 5 Not Used

1

(Logic Ground is approximately 0.4V above DeviceNet V-measured at the module).