Troubleshoot with the indicators – Rockwell Automation 1792D-2BVA2D ArmorBlock MaXum 2 Input with Alarm/2 Output Module Series B User Manual

Page 9

Advertising
background image

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 9

Publication 1792D-IN015B-EN-P - September 2000

The word/bit definitions are explained below.

The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our website at
http://www.ab.com/networks for producer/consumer technology
information and updates.

Troubleshoot with the Indicators

This module has the following indicators:

• Network/Module status indicator
• Logic status indicators
• Auxiliary power indicators
• Individual point status indicators for inputs 0 and 1 and

outputs 0 and 1

Byte

Bit

Description

Produces 0

00-01

02-03
04

05

06

07

Input status bits: When the bit is set (1), the input is on. Bit
00 = input 0, bit 01= input 1.
Alarm Status bit: Bit 02=Alarm A0, bit 03=Alarm A1.
Input Short Circuit Fault (ISC): ISC-A indicates a short circuit
for input 0.
Input Short Circuit Fault (ISC): ISC-B indicates a short circuit
for input 1.
Input Off Wire Fault (OW): OW-A indicates an off wire fault
for input 0.
Input Off Wire Fault (OW): ISC-B indicates an off wire fault
for input 1.

Produces 1

00-01

02-05
06

07

Output No load or Overload Fault (OFLT): When the bit is set
(1) an output fault has occurred. OFLT0=output 0,
OFLT1=output 1.
Reserved
Output Power Fault (OPWR): When the bit is set (1), Auxiliary
Power is not present.
Reserved

Consumes 0

00-01

02-07

Output bits: When the bit is set (1), the output will be turned
on. Bit 00=output 0, bit 01=output 1.
Reserved