Connect the Input Cord Sets to the MaXum Module

This module uses 5 pole micro (12mm) style PCB mounted
connectors.

Eight micro caps cover the connectors on your module. Remove the
caps and connect your cables to the appropriate ports. This product
has two inputs per connector. Use a “Y” splitter cable for access to all
input connections.

Use the micro caps to cover and seal unused ports. A pinout diagram
for the connectors is shown next.

Please refer to publication 889-5.0 for Rockwell Automation cables
and cord sets offerings.

Align the
screws to
properly
assemble the
module to the
base.

Cable Base 1792D-CBFM is
used for this example.

30724-M

Assembled
dimensions in (mm)

1.9 (48.26)

2.7 (68.6)

6.85 (174mm)

41452

Input Micro-Connector

(View into Socket)

Pin 1 Sensor Source Voltage
Pin 2 Input B

Pin 3 Return Logic Ground

1

Pin 4 Input A
Pin 5 Not Used

1Logic Ground is approximately 0.4V above DeviceNet V-measured at the module.