ArmorBlock MaXum 16 Input Module Series B 7

Publication 1792D-IN016B-EN-P - September 2000

DeviceNet Cable

DeviceNet cables are described in the installation publications for the
cable base of your choice. Refer to the following publications:

1792D-IN009B-EN-P ArmorBlock MaXum Cable Base
Installation Guide

DN-6.7.2 DeviceNet Cable Planning and Installation Manual

Communicate With Your ArmorBlock MaXum Module

This ArmorBlock module’s I/O is exchanged with the master through
a polled, change-of-state, or cyclic connection.

The module consumes and produces input data as follows:

Cyclic - allows configuration of the block as an I/O client. The block
will produce its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. The 16 input module scans the inputs and
fault bits producing a response that reflects their status.

Change of State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the module is alive
and ready to communicate.

Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

0 Byte

4 Bytes

Polled

0 Byte

4 Bytes

Change-of-State

0 Byte

4 Bytes

Bit

07

06

05

04

03

02

01

00

Produces 0

I7

I6

I5

I4

I3

I2

I1

I0

Produces 1

I15

I14

I13

I12

I11

I10

I9

I8

Produces 2

ISC-H

ISC-G

ISC-F

ISC-E

ISC-D

ISC-C

ISC-B

ISC-A

Produces 3

OW-H

OW-G

OW-F

OW-E

OW-D

OW-C

OW-B

OW-A

Where: OW = Off Wire I = Input ISC = Input Short Circuit in Sensor Source Voltage