Rockwell Automation 1792D-16BVTOD ArmorBlock MaXum 16 Input Module Series B User Manual

Page 8

Advertising
background image

8 ArmorBlock MaXum 16 Input Module Series B

Publication 1792D-IN016B-EN-P - September 2000

The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our website at
http://www.ab.com/networks for producer/consumer technology
information and updates.

Byte

Bit

Description

Produces 0

00-07

Input status bits: When the bit is set (1), the input is on. Bit
00 = input 0, bit 01= input 1, bit 02 = input 2, bit 03 =
input 3, bit 04 = input 4, bit 05 = input 5, bit 06 = input 6,
bit 07 = input 7.

Produces 1

00-07

Input status bits: Bit 00 = input 8, bit 01= input 9, bit 02 =
input 10, bit 03 = input 11, bit 04 = input 12, bit 05 = input
13, bit 06 = input 14, bit 07 = input 15.

Produces 2

00-07

Sensor source voltage, input short circuit (ISC): Fault bits
are set (1) when the sensor source voltage is faulted. Bit 00
= ISC-A on connector A, bit 01 = ISC-B on connector B, bit
02 = ISC-C on connector C, bit 03 = ISC-D on connector D,
bit 04 = ISC-E on connector E, bit 05 = ISC-F on connector
F, bit 06 = ISC-G on connector G, bit 07 = ISC-H on
connector H.

Produces 3

00-07

Off-Wire fault (OW): Bit 00 = OW-A on connector A, bit 01 =
OW-B on connector B, bit 02 = OW-C on connector C, bit
03 = OW-D on connector D, bit 04 = OW-E on connector E,
bit 05 = OW-F on connector F, bit 06 = OW-G on connector
G, bit 07 = OW-H on connector H.

Where: OW = Off Wire I = Input ISC = Input Short Circuit in Sensor Source Voltage