Troubleshoot with the Indicators
This module has the following indicators:
•
Network and Module status indicator
•
Logic status indicator
•
Individual point status indicators for inputs 0, through 15
The following table describes network and module status indicators.
Net/Mod Status Indicator
Indicator
Status
Off
No power or auto bauding
Flashing Green/Off On line but not connected
Solid Green
On line, link OK, connected
Flashing Red
Recoverable fault - module configuration error
I/O connection fault - one or more I/O connections in the timed-out
state
Solid Red
Unrecoverable fault
Communication failure - duplicate node address present or incorrect
baud rate
Green to Red to Off At powerup only - LED test
30722-M