IMPORTANT

If the BAT LED turns on when you apply power to the
controller, the battery life may be less then the table
below indicates. Some of the battery life may have been
used up while the controller was off and unable to turn
on the BAT LED.

Table 1 Worst-case estimates of life for the 1756-BATA battery

Controller:

Temp:

Time before BAT LED turns on:

Time after BAT LED
turns on and then
power off 100%:

Power
off 100%

Power
off 50%

Yearly
decrease:

1756-L55M12

1756-L55M13

60° C

190 days

396 days

11%

190 days

25° C

299 days

562 days

5%

299 days

0° C

268 days

562 days

6%

268 days

1756-L55M14

60° C

130 days

270 days

11%

139 days

25° C

213 days

391 days

5%

228 days

0° C

180 days

381 days

6%

193 days

1756-L55M16

60° C

71 days

160 days

13%

76 days

25° C

133 days

253 days

5%

142 days

0° C

105 days

220 days

6%

112 days

1756-L55M22

1756-L55M23

Use the values for the 1756-L55M13 controller.

1756-L55M24

Use the values for the 1756-L55M14 controller.

1756-L61

1756-L62

1756-L63

60° C

98 days

204 days

11%

104 days

25° C

146 days

268 days

5%

157 days

0° C

105 days

222 days

6%

113 days