Configuration data file – Rockwell Automation 1769-BOOLEAN Compact I/O BOOLEAN Module Installation Instructions User Manual

Page 13

Advertising
background image

13

Publication 1769-IN077A-EN-P - May 2006

Configuration Data File

The manipulation of bits from this file is normally done with programming software (for
example, RSLogix 500 software or RSNetWorx for DeviceNet software) during initial
configuration of the system. In that case, graphical screens provided by the programming
software simplify configuration.

Some systems, like the 1769-ADN DeviceNet adapter system, also allow the bits to be altered
as part of the control program using communication rungs. In that case, it is necessary to
understand the bit arrangement. Words 0 and 1 of the configuration data file set the input
control parameters for the module. Words 2 to 7 set the alternate output state operation of
the module. Each output point’s operating parameters are controlled by a group of eight
words.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Input Filter

1

IT_

I7

EI_

I7

IT_

I6

EI_

I6

IT_

I5

EI_

I5

IT_

I4

EI_

I4

IT_

I3

EI_

I3

IT_

I2

EI_

I2

IT_

I1

EI_

I1

IT_

I0

EI_

I0

2

PFE

3

4

PM3 PM2 PM1 PM0

5

PV3

PV2

PV1

PV0

6

FM3 FM2 FM1 FM0

7

FV3

FV2

FV1

FV0

8

IT_O0

EI_

O0

DB_

0

9

Operand_A_0

10

Operand_B_0

11

Operand_C_0

12

Operator_

2_0

Operator_

1_0

13

Output Delay 0

14

Output Duration 0

15

16

IT_O1

EI_

O1

DB_

1

17

Operand_A_1

18

Operand_B_1

19

Operand_C_1