8

Publication 1769-IN077A-EN-P - May 2006

Mount Expansion I/O

Minimum Spacing

Maintain spacing from
enclosure walls, wireways, or
adjacent equipment. Allow
50 mm (2 in.) of space on all
sides for adequate
ventilation, as shown.

Mount Module to Panel

Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws.
Mounting screws are required on every module.

Mount Module to Panel Using the Dimensional Template

Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and
one-and-a-half-wide modules (for example, the 1769-OA16 module).

ATTENTION

During panel or DIN rail mounting of all devices, be sure that all debris,
that is, metal chips or wire strands, is kept from falling into the module.
Debris that falls into the module could cause damage when cycling power.

Controller

Compact I/O

Compact I/O

Compact I/O

Compact I/O

Compact I/O

End Cap

Top

Bottom

Side

Side

Spacing for single-wide modules 35mm (1.378 in.)

Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)

Refer to host controller documentation for this dimension.

Host Controller

Note: Overall hole spacing
tolerance:

±

0.4mm (0.016 in.).

30535-M