Rockwell Automation 1769-BOOLEAN Compact I/O BOOLEAN Module Installation Instructions User Manual

Page 24

Advertising
background image

24

Publication 1769-IN077A-EN-P - May 2006

(3)

Sourcing Output - Source describes the current flow between the I/O module and the field device. Sourcing output circuits
supply source current to sinking field devices. Field devices connected to the negative side (dc common) of the field power
supply are sinking field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used
options.

Environmental Specifications

Specification

Value

Storage Temperature

-40…+85 °C (-40…+185°F)

Operating Temperature

0…60 °C (32…140 °F)

Operating Humidity

5…95% non-condensing

Operating Altitude

2000 m (6561 ft)

Vibration

Operating: 10…500 Hz, 5 g, 0.030 in. max peak-to-peak

Shock

Operating: 30 g panel mounted (20 g DIN-rail mounted)

Non-operating: 40 g panel mounted (30 g DIN-rail mounted)

Radiated and Conducted
Emissions

EN50081-2 Class A

Electrical /EMC

The module has passed testing at the following levels

ESD Immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC1000-4-3)

10V/m, 80…1000 MHz, 80% amplitude

Fast Transient Burst (IEC1000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC1000-4-5)

2 kV common mode, 1 kV differential mode

Conducted Immunity (IEC1000-4-6)

10V, 0.15…80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30…1000 MHz.

Certifications

Certification

Value

Agency Certification

• C-UL certified (under CSA C22.2 No. 142)

• UL 508 listed

• CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D

(UL 1604, C-UL under CSA C22.2 No. 213)

Advertising