Rockwell Automation 1769-BOOLEAN Compact I/O BOOLEAN Module Installation Instructions User Manual

Page 23

Advertising
background image

23

Publication 1769-IN077A-EN-P - May 2006

Off-state Current, Max

1.5 mA

On-state Voltage, Min

10V dc

On-state Current, Min

2.0 mA

Inrush Current, Max

250 mA

Nominal Impedance

2.0 kohm @ 24V dc

2.3 kohm @ 30V dc

IEC Input Compatibility

Type 1+

Input Point to Bus (CompactBus)
Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 s or
1697V dc for 1 s

75V dc working voltage (IEC Class 2 reinforced insulation)

(1)

Sinking Input - Sink describes the current flow between the I/O module and the field device. Sinking I/O circuits are driven
by a current sourcing field device. Field devices connected to the positive side (+V) of the field supply are sourcing field
devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.

Output Specifications

Voltage Category

24V dc

Operating Voltage Range

20.4…26.4V dc (source

(3)

)

Number of Outputs

4

Signal Delay, Max (Resistive Load)

Turn-on: 10 µs, output on-state current > 5 mA

Turn-off: 10 µs, output on-state current > 5 mA

Off-state Leakage, Max

(1)

(1)

Typical Loading Resistor - To limit the effects of leakage current through solid state outputs, a loading resistor can be
connected in parallel with your load. Use a 5.6 kohm, 1/2 W resistor for transistor outputs, 24V dc operation.

1.0 mA @ 26.4V dc

On-state Current, Min

1.0 mA

On-state Voltage Drop, Max

1.0V dc @ 1.0 A

Continuous Current per Point, Max

0.5 A @ 60 °C (140 °F)

1.0 A @ 30 °C (86 °F)

Refer to Temperature Derating on page 25.

Surge Current, Max

(2)

(2)

Recommended Surge Suppression - Use a 1N4004 diode reverse-wired across the load for transistor outputs switching 24V
dc inductive loads. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication 1770-4.1.

2.0 A (Repeatability is once every 2 s for a duration of 10 ms.)

Output Point to Bus (CompactBus)
Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 s or
1697V dc for 1 s

75V dc working voltage (IEC Class 2 reinforced insulation)

Input Specifications

Advertising