Rockwell Automation 1792D-16BVT0CD ArmorBlock MaXum 16 Input Module with Complete Diagnostics User Manual

Page 11

Advertising
background image

ArmorBlock MaXum 16 Input Module with Complete Diagnostics 11

Publication 1792D-IN053A-EN-P - August 2002

Byte

Bit

Description

Produced 0

00-07

Input status bits: When the bit is set (1), the input is on.
Bit 00 = input 0, bit 01= input 1, bit 02 = input 2, bit 03 = input 3,
bit 04 = input 4, bit 05 = input 5, bit 06 = input 6, bit 07 = input 7.

Produced 1

00-07

Input status bits: Bit 00 = input 8, bit 01= input 9, bit 02 = input
10, bit 03 = input 11, bit 04 = input 12, bit 05 = input 13,
bit 06 = input 14, bit 07 = input 15.

Produced 2

00-07

Sensor source voltage, input short circuit (ISC): Fault bits are set
(1) when the sensor source voltage is faulted.
Bit 00 is ISC-0 = a short circuit for input 0
Bit 01 is ISC-1 = a short circuit for input 1
Bit 02 is ISC-2 = a short circuit for input 2
Bit 03 is ISC-3 = a short circuit for input 3
Bit 04 is ISC-4 = a short circuit for input 4
Bit 05 is ISC-5 = a short circuit for input 5
Bit 06 is ISC-6 = a short circuit for input 6
Bit 07 is ISC-7 = a short circuit for input 7

Produced 3

00-07

Sensor source voltage, input short circuit (ISC): Fault bits are set
(1) when the sensor source voltage is faulted.
Bit 00 is ISC-8 = a short circuit for input 8
Bit 01 is ISC-9 = a short circuit for input 9
Bit 02 is ISC-10 = a short circuit for input 10
Bit 03 is ISC-11 = a short circuit for input 11
Bit 04 is ISC-12 = a short circuit for input 12
Bit 05 is ISC-13 = a short circuit for input 13
Bit 06 is ISC-14 = a short circuit for input 14
Bit 07 is ISC-15 = a short circuit for input 15

Produced 4

00-07

Off-Wire fault (OW):
Bit 00 is OW-0 = an off-wire fault for output 0
Bit 01 is OW-1 = an off-wire fault for output 1
Bit 02 is OW-2 = an off-wire fault for output 2
Bit 03 is OW-3 = an off-wire fault for output 3
Bit 04 is OW-4 = an off-wire fault for output 4
Bit 05 is OW-5 = an off-wire fault for output 5
Bit 06 is OW-6 = an off-wire fault for output 6
Bit 07 is OW-7 = an off-wire fault for output 7

Produced 5

00-07

Off-Wire fault (OW):
Bit 00 is OW-8 = an off-wire fault for output 8
Bit 01 is OW-9 = an off-wire fault for output 9
Bit 02 is OW-10 = an off-wire fault for output 10
Bit 03 is OW-11 = an off-wire fault for output 11
Bit 04 is OW-12 = an off-wire fault for output 12
Bit 05 is OW-13 = an off-wire fault for output 13
Bit 06 is OW-14 = an off-wire fault for output 14
Bit 07 is OW-15 = an off-wire fault for output 15

Where: I = Input ISC = Input Short Circuit in Sensor Source Voltage OW = Off Wire

Advertising