This product has been tested at an Open DeviceNet Vendor
Association, Inc. (ODVA) authorized independent test laboratory and
found to comply with ODVA Conformance Test. Please contact the
ODVA website (http://www.odva.org) for listing of products tested by
ODVA independent test labs for further details.

General Specifications (cont.)

EFT/B Immunity

IEC 61000-4-4:
±4kV at 2.5kHz on signal ports
±4kV at 2.5kHz on power ports
±2kV at 5kHz on communications ports

Surge Transient Immunity

±500V line-line(DM) and ±500V line-earth(CM) on signal
ports
+2kV line-earth (CM) on shielded ports
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Certifications
(when product is marked)

CSA

CSA Certified Process Control Equipment

CSA

CSA Certified Process Control Equipment for

Class I, Division 2 Group A,B,C,D Hazardous
Locations

CE

3

European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity

C-Tick

3

Australian Radiocommunications Act, compliant
with:
AS/NZS 2064; Industrial Emissions

ODVA

ODVA conformance tested to DeviceNet
specifications

Technical Data (user information)

Publication 1792-TD001

1.

You use this conductor category information for planning conductor routing as described in the
system level installation manual.

2.

See publication 1770-4.1, “Programmable Controller Wiring and Grounding Guidelines.”

3.

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.