Specifications – Rockwell Automation 1792D-16BVT0CD ArmorBlock MaXum 16 Input Module with Complete Diagnostics User Manual

Page 13

Advertising
background image

ArmorBlock MaXum 16 Input Module with Complete Diagnostics 13

Publication 1792D-IN053A-EN-P - August 2002

The following table describes logic status indicators.

The following table describes individual I/O status indicators.

For more information on indications see the Technical Data
publication 1792-TD001.

Specifications

Net/Mod Status Indicator

Indicator

Status

Solid Red

Unrecoverable fault

Communication failure - duplicate node address present or incorrect
baud rate

Green to Red to Off At powerup only - LED test

Logic Status Indicators

State

Status

Off

Logic is disabled

Solid Green

Logic is enabled

Flashing Green

Local forces are applied and local logic is enabled

I/O Status Indicators

Function

Module Status Indicator

Point Indicator Condition

Inputs

Green
Green
Module status blink red
Module Status blink red

None
Yellow
Red

1

Blink Red

1

No valid input
Valid input
Short on input A or B
Off-Wire on input A or B

1

The top LED of the pair associated with a connector will provide the diagnostic indicator.

Individual diagnostic information is produced over DeviceNet.

16 Input Module - Cat. No. 1792D-16BVTOCD

Input Specifications

Max.

Min.

Inputs per block

16 - 3 wire or dry contact PNP or NPN devices or 8 - 4 wire
PNP or NPN devices

Sensor Source Current (per input)

50mA

On-state Voltage - Sinking

25V dc

10V dc

On-state Voltage - Sourcing

(SSV-10)V dc

-

On-state Current

10mA

2mA

Off-state Voltage - Sinking

5V dc

-