Rockwell Automation 1792D-16BVT0CD ArmorBlock MaXum 16 Input Module with Complete Diagnostics User Manual

Page 8

Advertising
background image

8 ArmorBlock MaXum 16 Input Module with Complete Diagnostics

Publication 1792D-IN053A-EN-P - August 2002

This module uses 5 pole micro (12mm) style PCB mounted
connectors.

Eight micro caps cover the connectors on your module. Remove the
caps and connect your cables to the appropriate ports. This product
has two inputs per connector. Use a “Y” splitter cable for access to all

input connections.

Use the micro caps to cover and seal unused ports. A pinout diagram
for the connectors is shown next.

Use Rockwell Automation Y-cables 879D-F4ACDM5-x, where
x=length in meters (0M3, 1, 2, 3, 5, 10). Please refer to publication
C114-CA001 for other Rockwell Automation cables and cord sets
offerings.

IMPORTANT

If the devices (sensors) connected to the input connections
require Class 2 power to operate, the DeviceNet connections
of this equipment must be powered by a Class 2 source.

WARNING

!

When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with
proper wiring method that complies with the governing
electrical codes.

41452

Input Micro-Connector

(View into Socket)

Pin 1 Sensor Source Voltage A
Pin 2 Input B

Pin 3 Return Logic Ground

1

Pin 4 Input A
Pin 5 Sensor Source Voltage B

1

Logic Ground is approximately 0.4V above DeviceNet V-measured at the module.