Plc 3 family example – Rockwell Automation 1771-IE,D17716.5.7 ANAL.INPUT MOD. User Manual
Page 23

Programming the Analog Input Module
Chapter 4
4Ć4
This rung adds up to 0.13ms to the processor scan time so use it sparingly.
Locate it at the beginning of your ladder program. This logic is not
required for PLC-2 family remote systems or for any other processor
family.
This example is written for the following conditions (Figure 4.3).
The module resides in rack 1, module group 2, slot 0
8-word block transfer
BTR control address is
FB001:0000
BTR file address is
FB002:0001
MVF source file A is
FB002:0001
MVF destination file R is
FB003:001
MVF counter address is
C000l
MVF number of words moved is 8
MVF rate per scan is
all/scan
Figure 4.3
Example Program for PLCĆ3 Family Processors
LE
BTR
BLOCK TRANSFER READ
RACK :
GROUP :
MODULE :
DATA :
001
2
0=LOW
FB002:0001
DN
LENGTH =
CNTL :
8
FB001:0000
ER
EN
MVF
FILES FROM A TO R
A :
R :
COUNTER :
POS/LEN =
DN
12
C0001
15
WB001:0000
WB001:0000
15
CNTL
12
CNTL
15
CNTL
13
15
(DN)
C0001
ER
C0001
13
(DN)
FB002:0001
FB003:0001
C0001
8
MODE=
ALL/SCAN
PLCĆ3 Family Example