Calibrating the Analog Input Module

Chapter 5

5Ć6

Figure 5.2

Location of Potentiometers and Test Points

14163

Potentiometer #1
Potentiometer #2
Potentiometer #3

Red Test Point
Black Test Point

8.

Seal the setting with a drop of sealant.

9.

Turn off power to the external power supply, I/O chassis, and
processor.

10. Remove the module from the I/O chassis.

11. Reset switch number 2 OFF of the transfer mode switch assembly.

12. After replacing the covers, place the module back in its slot in the

I/O chassis.

Start your calibration procedure here if your input range is NOT (1 to 5
VDC) or (4 to 20 mA).

You make one adjustment for all channels at the same time for offset, then
one adjustment for gain calibration.

Offset (Part B)