Input channels, How analog modules – Rockwell Automation 1771-IE,D17716.5.7 ANAL.INPUT MOD. User Manual

Page 6

Advertising
background image

Overview of the Analog Input Module

Chapter 2

2Ć2

manipulate values representing temperature, pressure, rotational speed,
light intensity, and position.

A wiring arm (cat. no. 1771-WB) accompanies the module. It acts as a
terminal strip for input connections. The wiring arm pivots on the I/O
chassis to connect with terminals on the front of the input module. Thus,
the wiring arm lets you quickly connect or disconnect your input wiring
when inserting or removing the input module from the I/O chassis.

The input module meets the requirements of the Instrument Society of
America, Standard S50.1 (1975), “Compatibility of Analog Signals for
Electronic Industrial Process Instruments.”

The input module supports eight single-ended input channels. All eight
channels have the same voltage or current range that you select when
ordering the module. The range is factory set and calibrated.

Nominal Range:

Precise Range:

Units/Bit:

Order

Code

1 to 5 V

4 to 20mA

1 to 4.9844 V

4 to 19.937 mA

15.60 mV/bit

0.063 mA/bit

01

05

0 to 5 V

0 to 20 mA

0 to 4.980 V

0 to 19.922 mA

19.53 mV/bit

0.078 mA/bit

02

06

Ć10 to 10V

Ć10 to 9.922V

78.13 mV/bit

03

Ć20 to 20 mA

Ć20 to 19.844

mA

0.156 mA/bit

07

0 to 10 V

0 to 9.96 V

39.06 mV/bit

04

When ordering 1771-IE modules, place the order code as a suffix to the
catalog number. For example, 1771-IE-04.

You can change from a voltage range to the equivalent current range and
vice versa within limited catagories. For example, from the above table
you can switch from a range of (1 to 5 VDC) to (4 to 20 mA) or (0 to 5
VDC) to (0 to 20 mA) without recalibrating.

Analog input modules communicate with a programmable controller by
block transfer in the following manner (Figure 2.2).

Input Channels

How Analog Modules

Communicate With

Programmable Controllers

Advertising