Calibrating the Analog Input Module

Chapter 5

5Ć4

Set these switches as follows:

1.

Range Select switch assembly lets you select a current or voltage
input range by setting switches 1-10. These switch settings remain
the same during and after calibration.

Change these switch settings only if you want to change to another
voltage or current input range group.

Range:

Switch Number

1

2

3

4

5

6

7

8

9

10

1 to 5V

4 to 20 mA

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

ON

ON

OFF

OFF

ON

ON

OFF

OFF

OFF

OFF

0 to 5V

0 to 20 mA

ON

ON

ON

ON

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

ON

ON

OFF

OFF

ON

ON

0 to 10V

ON

ON

OFF

OFF

ON

ON

OFF

ON

OFF

OFF

+10V

ON

ON

OFF

OFF

ON

OFF

ON

OFF

ON

OFF

+20mA

ON

ON

OFF

OFF

ON

OFF

ON

ON

OFF

OFF

2.

Signal Mode switch assembly lets you select current mode (all
switches are ON) or voltage mode (all switches are OFF).

CAUTION: Be sure external power (15, 5 VDC) is OFF before
changing the signal mode switch.

Set all eight switches to OFF (voltage mode) during calibration.

3.

Transfer Mode switch assembly lets you select single transfer (switch
1 ON) or block transfer (switch 1 OFF).

Change the setting of switch 2 to ON only for the Offset (Part A)
procedure.

This procedure applies only if your input range is (1 to 5 VDC) or (4 to 20
mA).

Important: If the input range of your module is other than a range of (1
to 5 VDC) or (4 to 20 mA), skip this procedure and go directly to Offset
(Part B).

Offset (Part A)