Overview of the analog input module chapter 2 – Rockwell Automation 1771-IE,D17716.5.7 ANAL.INPUT MOD. User Manual

Page 9

Advertising
background image

Overview of the Analog Input Module

Chapter 2

2Ć5

Figure 2.4

Analog Input Word

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

0 0

Overflow/

Underflow Bit

0 = within range

1 = out of range

High Byte

Low Byte

Channel

Address

(see table)

Most

Significant

Digit

(0-2)

Middle

Digit

(0-9)

Least

Significant

Digit

(0-9)

14165

Bits

16 15 14
0 0 0

0 0 1

0 1 0

0 1 1

1 0 0

1 0 1

1 1 0

1 1 1

Channel

Number

1

2

3

4

5

6

7

8

Channel Address Codes

Bits 00-11 These bits contain input values which range from 0 to 255
BCD (8 bit resolution).

Bits 12-13 These bits must remain reset (to 0) for proper operation.

Bits 14-16 These bits indicate by binary code which channel is being
read.

Bit 17 This bit indicates an overflow/underflow condition, and is set (to 1)
under the following conditions:

input value is zero or negative
input value is greater than or equal to 255

Advertising