GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 13

Publication 1753-IN011A-EN-P - October 2005

Surge on Digital Inputs

An EN 61000-4.5 surge impulse can be read as a short duration HI signal. To avoid
an error:

• install shielded input lines to prevent effects of surges in the system, or
• implement software filtering in the user program. A signal must be present

for at least two cycles before it is used by the rest of the logic in the user
program.

Line Control

Line control is a short-circuit and line break monitoring system (for example, E-Stop
inputs) which can be configured for the GuardPLC system.

57

11

Digital input 11

58

12

Digital input 12

59

L-

Reference pole

60

L-

Reference pole

61

Ground

Shield

62

Ground

Shield

63

LS+

Sensor supply for inputs 13 to 16, 40 mA buffered/1 A non-buffered

64

LS+

Sensor supply for inputs 13 to 16, 40 mA buffered/1 A non-buffered

65

13

Digital input 13

66

14

Digital input 14

67

15

Digital input 15

68

16

Digital input 16

69

L-

Reference pole

70

L-

Reference pole

71

Ground

Shield

72

Ground

Shield

IMPORTANT

For information on how to configure inputs and outputs for line
control, see the GuardPLC System User Manual, publication
number 1753-UM001.