18 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module

Publication 1753-IN011A-EN-P - October 2005

3-pole Connection With Line Monitoring

Two 2-pole channels can support dual channel devices with only a single reference
connection. If line monitoring is required, the channels must be configured in pairs,
using the DO[xx][xx].in pairs system parameter. There are four pairs allowed:

• channels 1 and 2,
• channels 3 and 4,
• channels 5 and 6,
• and channels 7 and 8.

Line monitoring is accomplished by switching off one channel while the second
channel is tested for wiring faults.

A detected line fault is reported by the module’s error codes.

ATTENTION

Inductive loads must be connected with a protection diode on the
load in 3-pole connection.

Load

(drive, valve)

1753-IB16XOB8