Rockwell Automation 1753-IB16XOB8 GuardPLC 16-Digital Inputs and 8-Digital Outputs Installation Instructions User Manual

Page 19

Advertising
background image

GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 19

Publication 1753-IN011A-EN-P - October 2005

Digital Output Terminals

See page 22 for the appropriate wire size. Digital outputs are connected to the

following terminals:

Terminal Number

Designation

Function

1

S+

Reference pole for negative-switching digital outputs

2

S+

Reference pole for negative-switching digital outputs

3

S+

Reference pole for negative-switching digital outputs

4

S+

Reference pole for negative-switching digital outputs

5

S-

Reference pole for positive-switching digital outputs

6

S-

Reference pole for positive-switching digital outputs

7

S-

Reference pole for positive-switching digital outputs

8

S-

Reference pole for positive-switching digital outputs

9

1-

Digital output 1, negative-switching

10

1+

Digital output 1, positive-switching

11

2-

Digital output 2, negative-switching

12

2+

Digital output 2, positive-switching

13

3-

Digital output 3, negative-switching

14

3+

Digital output 3, positive-switching

15

4-

Digital output 4, negative-switching

16

4+

Digital output 4, positive-switching

17

5-

Digital output 5, negative-switching

18

5+

Digital output 5, positive-switching

19

6-

Digital output 6, negative-switching

20

6+

Digital output 6, positive-switching

21

7-

Digital output 7, negative-switching

1

2

3

4

5

6

8

7

S+

DO

DO

S+ S+ S+ S- S- S- S-

9 10 11 12 13 14

16

15

1- 1+ 2- 2+ 3- 3+

4+

4-

5- 5+ 6- 6+ 7- 7+

8+

8-

17 18 19 20 21 22

24

23

Advertising