Specifications – Rockwell Automation 1753-IB16XOB8 GuardPLC 16-Digital Inputs and 8-Digital Outputs Installation Instructions User Manual

Page 22

Advertising
background image

22 GuardPLC 16-Digital Inputs and 8-Digital Outputs Module

Publication 1753-IN011A-EN-P - October 2005

Specifications

Module

Response Time

≥ 10 ms

Interface: GuardPLC
Ethernet

2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch

Operating Voltage

24V dc, -15% to +20%, w

ss

≤ 15%

Current Consumption

max. 10 A (with max. load)
0.6 A @ 24V idle current

Isolation Voltage

No isolation between circuits

Wiring Category

(1)

category 2 on communications ports, signal ports, and power ports

Wire Size

I/O – 16 AWG (1.5 mm

2

) to 26 AWG (0.14 mm

2

) solid or stranded copper wire

rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm) insulation max.

Power – 14 AWG (2.5 mm

2

) to 22 AWG (0.34 mm

2

) solid or stranded copper wire

rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm) insulation max.

Terminal Block Torque

0.51 Nm (4.5 in-lb)

Fuse (external)

12 A (slow blow)

Battery Backup

none

Digital Inputs

No. of Inputs

16 (not electrically isolated)

On-state

Voltage: 15V to 30V dc
Current Consumption:

≥ 2 mA @ 15V

Off-state

Voltage: max. 5V dc
Current Consumption: max 1.5 mA (1.

0 mA @ 5V)

Switching Point

typically 7.5V

Supply

4 supplies @ 24V dc/40 mA short-circuit proof, buffered for 20 ms
2 supplies @ 24V dc/1 A short-circuit proof, non-buffered

Digital Outputs

No. of Outputs (L+)

8 (not electrically isolated), reference pole S-

No. of Outputs (L-)

8 (not electrically isolated), reference pole S+

Output Voltage

≥L+ minus 2V

Output Current (L+)

Output Current (L-)

Channels 2, 4, 5, and 7: 0.5 A @ 60°C (140°F)
Channels 1 and 8: 1 A @ 60 °C (140 °F); 2 A @ 40 °C (104 °C)
Channels 3 and 6: 1 A @ 60 °C (140 °F)

Max. lamp load

25 W

Max. inductive load

500 mH

Minimum Load

2 mA per channel

Internal Voltage Drop

max. 2.0V dc @ 2 A

Off-State Leakage Current

max. 1 mA @

2V

Overload Response

Shut down of the concerned output with cyclic reconnection