Troubleshoot with led indicators – Rockwell Automation 1753-IB16XOB8 GuardPLC 16-Digital Inputs and 8-Digital Outputs Installation Instructions User Manual

Page 21

Advertising
background image

GuardPLC 16-Digital Inputs and 8-Digital Outputs Module 21

Publication 1753-IN011A-EN-P - October 2005

Troubleshoot with LED Indicators

Indicator

State

Condition

24V dc

On

24V dc operating voltage present.

Off

No operating voltage.

RUN

On

This is the normal status of the module.
A routine, which has been loaded into the module, is executed.
The module processes input and output signals, carries out communication and
performs hardware and software tests.

Flashing

The module is in STOP mode and is not executing a routine.
All system outputs are reset.
STOP mode can be triggered by setting the Emergency stop system variable to TRUE
in the routine, or by direct command from the programming software.

Off

The module is in ERROR_STOP (see ERROR).

ERROR

On

• A hardware error has been detected by the module. The module goes to

ERROR_STOP and the execution of the routine is halted. Hardware errors are
errors in the module, errors in one or more of the digital input and output
modules, or errors in the counters.

• A software error in the operating system has been detected by the module.

• The watchdog has reported an error due to exceeded cycle time.
All system outputs will be reset and the module ceases all hardware and software
tests. The module can only be restarted by a command from the programming
software.

Off

No errors are detected.

PROGress

On

The upload of a new module configuration is in progress.

Flashing

The upload of a new operating system into the Flash ROM is in progress.

Off

No upload of module configuration or operating system in progress.

FORCE

On

The module is executing a routine (RUN) and FORCE mode is activated by the user.

Flashing

The module is in STOP, but Forcing has been initiated and will be activated when the
module is started.

Off

Forcing is OFF.

FAULT

On

• The routine (logic) has caused an error.

• The module configuration is faulty.

• The upload of a new operating system was not successful and the operating

system is corrupted.

Flashing

An error has occurred during a Flash ROM write cycle.
One or more I/O errors have occurred.

Off

None of the above errors has occurred.

OSL

Flashing

Emergency Operating System Loader is active.

BL

Flashing

Boot Loader unable to load operating system or unable to start COMM operating
system loader.

Module status can be interrogated through the programming software. For more information, refer to the
GuardPLC System User Manual, publication number 1753-UM001.

Advertising