14 ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B

Publication 1792D-IN051A-EN-P - February 2001

Specifications

8 Input Module - Cat. No. 1792D-8BVOD

Input Specifications

Max.

Min.

Inputs per block

8 - 3 wire or dry contact PNP or NPN devices or 8 -
4 wire PNP or NPN devices

Sensor Source Current (per input)

50mA

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

Off-Wire Sense Current

0.5mA

-

General Specifications

Indicators

Net/Mod Status - red/green
Logic Status - red/green
Point LED - yellow/orange/red

Communication Rate

125Kbps @ 500 meters(1600 feet) for thick cable,

flat media length 375 meters

250Kbps @ 200 meters(600 feet) for thick cable,

flat media length 150 meters

500Kbps @ 100 meters (330 feet) for thick cable,

flat media length 75 meters

DeviceNet Power Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.

25V dc max
200mA max (no sensors)

11V dc min up to
1.6A (8 sensors
@50mA per sensor)

Dimensions (assembled to base)
inches - (Millimeters)

1.9H x 2.7w x6.85D
(48.26)H x (68.6)W x (174)D

Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration

-25 to 60

o

(-13 to 140

o

F)

-25 to 80

o

C (-13 to 176

O

F)

Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11(+1)ms pulse width
Tested 10g @ 10-500Hz per IEC 68-2-6

Conductors

Publication 889-CP001A-US-P

Enclosure

Meets or exceeds IP67

Agency Certification
(when product is marked)

CSA certified
CSA Class I, Division 2, Groups A, B, C, D certified
UL listed
CE marked for all applicable directives

Technical Data (user information)

Publication 1792-TD001B-EN-P