Devicenet cables, Communicate with your armorblock maxum i/o module – Rockwell Automation 1792D-8BV0D ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B I.I. User Manual

Page 7

Advertising
background image

ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B 7

Publication 1792D-IN051A-EN-P - February 2001

DeviceNet Cables

DeviceNet cables are described in the installation publications for the
cable base assembly of your choice. Refer to the following
publications:

1792D-IN009B-EN-P ArmorBlock MaXum

Cable Base

Installation Guide

DN-6.7.2 DeviceNet Cable Planning and Installation Manual

Communicate With Your ArmorBlock MaXum I/O
Module

This ArmorBlock module’s I/O is exchanged with the master through
a poll, change-of-state, or cyclic connection.

The module consumes and produces I/O data as follows:

Cyclic - allows configuration of the block as an I/O client. The block
will produce its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. The 8 input module cans the inputs and fault
bits producing a response that reflects their status.

Change-of-State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the module is alive
and ready to communicate.

Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

0 Byte

3 Bytes

Polled

0 Byte

3 Bytes

Change-of-State

0 Byte

3 Bytes

Bit

07

06

05

04

03

02

01

00

Produced 0

I7

I6

I5

I4

I3

I2

I1

I0

Produced 1

ISC-H

ISC-G

ISC-F

ISC-E

ISC-D

ISC-C

ISC-D

ISC-A

Produced 2

OW-H

OW-G

OW-F

OW-E

OW-D

OW-C

OW-B

OW-A

Where: I = Input; ISC=Input Short Circuit in Sensor Source Voltage; OW= Off Wire