Rockwell Automation 1792D-8BV0D ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B I.I. User Manual

Page 8

Advertising
background image

8 ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B

Publication 1792D-IN051A-EN-P - February 2001

The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks for producer/consumer technology
information and updates.

Byte

Bit

Description

Produces 0

00-07

Input Status bits: When the bit is set (1), the input is on.
Bit 00 = input 0, bit 01 = input 1, bit 02 = input 2,
bit 03 = input 3, bit 04 = input 4, bit 05 = input 5,
bit 06 = input 6, bit 07 = input 7.

Produces 1

00-07

Sensor source voltage, input short circuit (ISC): Fault bits are
set (1) when the sensor source voltage is faulted.
Bit 00 = ISC-A on connector A, bit 01 = ISC-B on connector B,
bit 02 = ISC-C on connector C, bit 03 = ISC-D on connector D,
bit 04 = ISC-E on connector E, bit 05 = ISC-F on connector F,
bit 06 = ISC-G on connector G, bit 07 = ISC-H on connector H.

Produces 2

00-07

Off-Wire fault (OW): Bit 00 = OW-A on connector A,
bit 01 = OW-B on connector B, bit 02 = OW-C on connector C,
bit 03 = OW-D on connector D, bit 04 = OW-E on connector E,
bit 05 = OW-F on connector F, bit 06 = OW-G on connector G,
bit 07 = OW-H on connector H.

Advertising