Install the terminal, Required tools, Mounting clearances – Rockwell Automation 2711P-RDT12H High-bright Display Module User Manual

Page 11: Panel cutout dimensions

Advertising
background image

High-bright Display Modules 11

Publication 2711P-IN026E-EN-P - September 2008

Required Tools

These tools are required for installation:

Panel cutout tools

Small, slotted screwdriver

Torque wrench (lb

in)

Install the Terminal

Before installing the terminal in a panel, review these topics:

Mounting clearances

Panel cutout dimensions

Product dimensions

Mounting Clearances

Allow adequate clearance around the terminal, inside the enclosure, for adequate
ventilation. Consider heat produced by other devices in the enclosure. The ambient
temperature around the terminals must be between 0…55 °C (32…131 °F).

These minimum clearances are required for ventilation:

Top clearance: 51 mm (2 in.)

Bottom clearance: 102 mm (4 in.)

Side clearances: 25 mm (1 in.)

Back clearance: 25 mm (1 in.)

Minimum side clearance for insertion of memory card is 102 mm (4 in.).

Panel Cutout Dimensions

Use the full size template shipped with your terminal to mark the cutout
dimensions.

The 1250 Touch PanelView Plus and PanelView Plus CE Terminals are 257 mm
(10.11 in.) high and 338 mm (13.29 in.) wide.